# SPECIFICATIONS
Display LCD with dual color backlight
Wiring input 3 Ø 4 wire, 3 Ø 3 wire, 1 Ø 2 wire, 2 Ø 2 wire
Rated input voltage 11 to 300V AC (L-N) ; 50 to 520V AC (L-L)
Rated Input Current Nominal 5A AC (MIN-11mA MAX- 6A)
Burden 20 mOhms
Frequency Range 45-65 Hz
CT primary 1A / 5A to 9999A (programmable for any value)
CT Secondary 1A or 5A (Programmable)
PT Primary 100V to 500kV (Programmable for any value)
PT Secondary 100V to 500V (Programmable for any value)
Display update time 1sec for all parameters
Display scrolling Auto / Manual / Default (Programmable)
Display scrolling time 5 Sec.
Power Consumption MAX 15VA
Trip Indication Backlight turns to orange
Controlling Range Target PF: 0.800 lag to 0.800 lead
Switching Program : Automatic / Linear / Rotational
Relay Output Alarm mode :
Over Voltage, Under Voltage,
Over Compensate,
Under Compensate, CT Polarity error, No Voltage,
Step error, Over Temperature.
Temperature 0 to 100°C
Fan Output ON / OFF / Temp controlled
Environmental Conditions Outdoor use
Mounting Panel Mounting
Weight REM-C-312 : 460gms ; REM-308 : 450gms